X400 Web Relay
ControlbyWeb X400 Hardware Configuration Guide
See our Loadout Control Setup Article for setting up configuring the Fast-Weigh ticketing application for Asphalt Loadout. The following guide covers direct configuration of the X400 and its expansion modules.
Do not attempt configuration of this device without consulting a Fast-Weigh Project Manager or Support Team Member.

Networking Settings
X400 Default IP Address: 192.168.1.2
Directly connect your PC to the X400 and configure your Network Adapter to be on 192.168.1.1 gateway.
Open a web browser and enter "192.168.1.2/setup.html" in your address bar.
Default Username: admin
Default Password: webrelay
General Settings > Network Settings

Configure network settings to be compatible with local network that is running the Fast-Weigh Ticketing Application. If you are unsure of the settings required for your network, contact your network administrator / IT Department.

Enter "*" in the CORS Origin Field. (wildcard character)

Enable Remote Services
Set Certificate Request Method to "Certificate Request Token"
Certificate Request Token: provided by request
Devices
Go To Devices and Click Find Devices
A list should populate of all connected modules. If you do not see all modules, confirm that the ribbon cable connecting the x400 to the expansion modules is firmly connected.
Click Add Device

Name Device (EG: "DI 11 though 18" meaning Digital Input 1.1 through 1.8)
Click Save Changes
I/O Setup
Start with module closest to X400, confirm that labeled wires are going to "1.1". Names and Input Numbers will be based on referencing onsite schematics. Number of modules and order of wiring may vary between locations.
Start with module closest to X400, confirm that labeled wires are going to "1.1". Names and Input Numbers will be based on referencing onsite schematics. Number of modules and order of wiring may vary between locations.
Digital Inputs
Click "Add Expansion Digital Inputs +"

Rename each Digital Input based on the schematics.
There are two types of Digital Inputs. On/Off and Counter
On/Off Digital Inputs

On/Off Digital inputs will use the default settings, only requiring they be renamed to match the schematics
Counter Digital Inputs

Change Mode to "Counter"
Change Decimal Places to "0"
Rename Digital Input Name
Relays
Relays should use all default settings, only requiring they be renamed to match schematics
Monitor & Control
Go to control page setup

Add all I/O to control page for initial testing and long term status monitoring