Loadout Control Setup
Sync Config Setup
Admin Settings > Sync Configs > Silos
Click New Silo

Assign the Lane
Name the Silo (typically numbered)
Set the Capacity in tons (200 tons for example)
Set Type to "Pulse" (unless inventory is being monitored outside Fast-Weigh, then set to none)

Server Settings
Go To Server Settings
Open Beta Features

Enable Add/Edit Silos
Go to the Manage Silos Section
Click Add Silo

Select a Silo from the List to see the full configuration options:

Web Switch URL: Static URL of Web Switch, Port is NOT required by default but may be needed depending on networking solution
Freefall Amount: (Weight Threshold in LBS/KG) amount of material left in the drop to trigger the gate to close.
Auto Calculate Freefall: When enabled, an algorithm adjusts the free fall amount automatically based on tolerance differences in previous drops.
Sort: Changes the order in which the silos are display on the ticketing screen
Gate Relay #: Relay Number must match the Device Relay # (not the local) for the silo gate
Pulse Duration: (In Seconds) When a request is made to open the gate, it is kept open for this duration. Requests are made every half second.
Jog Time: Amount of time the gate is held open when a Jog is manually triggered
Slow Open Gate: When enabled, a separate relay can be designated as a slow/partial gate opening
Slow Open Relay #: Device Relay # (not local) for slow/partial gate opening
Slow Jog Time: Amount of time the gate is held open when a slow/partial Jog is manually triggered
Default # of Drops: Splits loads into number of drops
Drop n %: Drop percentages are automatically split equally between all drops, but can be configured to not be equal (for example with 3 drops: 1 - 40%, 2 - 30%, 3 - 30%)
Safety Inputs: Separate Pop up for configuring additional Safety Inputs, if the input state does not match, then Fast-Weigh will consider Loadout as NOT safe
Description: Name of Safety input (Example: Photoeye)
Digital Input #: Digital Device Input # (not local)
Input State: Indicate if On or Off is the safe state
Safety Selector: When enabled, a Digital Input can be configured to
Selector Digital Input #: Digital Device Input # (not local)
Gate Timer: (in Seconds) If no material is dropped within the time frame, the load is automatically cancelled
Max Drop Timer: (in Seconds) if the gate has been open for this long, the load is automatically cancelled
Signal on Load Complete: If enabled, the relay will be signaled when a ticket is created. Used for Horns or Traffic Lights
Load Complete Relay #: Device Relay # (not local)
Signal Duration: (In Seconds) duration of load complete signal
Load Lamp: When Enabled, the silo card will display a button that can enable the lamp until the button is deactivated. Silo Lamps tell drivers which silo they will be loaded from if the scale has more than one silo.
Lamp Relay #: Device Relay # (not local)
Lamp Pulse Time: no longer supported
High Inventory: When enabled, an indicator is displayed in app if a high inventory level is reached
High Inventory Digital Input #: Digital Device Input # (not local)
Sync Status Updates to Portal: Not currently supported